What is the setpoint range for a FRC-20 Variac motor control that is configured for limited range?

Submitted byglx25v onFri, 08/17/2018 - 17:29

When the controller is set for limited range then the full range of the setpoint or potentiometer signal will be the upper 1/3 of the range.

1) If the FRC-20 is configured for 0-150V then the setpoint signal range will be approximately 100-150V.

2) If the FRC-20 is configured for 0-300V then the setpoint signal range will be approximately 200-300V

3) If the FRC-20 is configured for 0-600V then the setpoint signal range will be approximately 400-600V.

Depending on the input voltage and the variable transformer used the full range of the FRC-20 may not be used.  For example a standard variable transformer has a 0-140VAC range.  The setpoint range will be 100-140V if settings for (1) above are used.


FRC-20 Installation Manual