Changing from thermocouple to RTD input on 2810 or 3810

Submitted byglx25v onFri, 08/17/2018 - 17:29

You must do the following to switch from thermocouple to RTD on the 2810 / 3810 series:

 
1) Remove the compensator from terminals 1 & 2 (on housing)
2) Change S1 input switch form thermocouple position to RTD position.
3) Set Switches S2/1 through S2/6 as per manual.
4) Enter the configuration mode and set to the appropriate range code.

Installation/operation manual is required to make this change:
Obsolete Manuals