Watlow Series 981-984
Uses Commanders Watlow 982 Modbus Table.
Commander does not support the method that Watlow uses for storing the ramp/dwell profile setpoints and therefore does not have the capability to display, change or view these values.
Watlow provides a Low and a High Alarm for each Alarm. Commander is setup to annunciate both conditions as standard. You can also edit the Commander Modbus Table to annunciate just the High or the Low alarm condition if desired.
From the Main Screen Menus:
Click Setup
Click Edit Modbus Tables
Select the Watlow 982 Table
Enter a value of “Decimal Places” for Alarm 1 Status and/or Alarm2 Status as below:
17 to annunciate both High & Low Alarms
13 to annunciate only High Alarms
14 to annunciate only Low Alarms
Commander has no provisions to signal open thermocouple conditions with this model.