SCR Power Controls rss button
There were 7 questions found in this category:
  1. questionCan heater life be improved by using SCR power controls?
    SCR power controls can extend the life of your heaters by reducing thermal stress on your heaters. The heaters are maintained at more constant temperatures reducing size changes in the heating elements due to temperature changes. Both zero fired and phase angle SCR controllers can improve the h ...

  2. questionCan tungsten heating elements be controlled with SCR controllers?
    SCR power controls can be used to control tungsten heating lamps. Phase angle control with extended soft start ramp is recommended. Use of this type of control will lengthen the life of the heating elements in most applications.For information on our SCR power controls:http://www.instrumentation ...

  3. questionDo SCR power controllers cause harmonics on the power lines?
    SCR power controls do generate harmonics on the power lines. A zero fired controller generates much less harmonic distortion and seldom creates problems. Most of its harmonics are below the utility frequency. Phase angle controllers generate harmonics above the utility frequency with the lar ...

  4. questionHow do I adjust the bias and gain on my SCR power control?
    Bias & Gain Adjustment The bias & gain must be properly adjusted so that the SCR power control responds properly to the input signal. ISE configures and adjusts the SCR power control prior to shipment. If reconfiguration or further adjustment is required the following procedure can be us ...

  5. questionMy SCR power control has full line voltage output all the time with no load connected.
    It is normal that the SCR control has full line output when no load is connected. This is caused by the small leakage that is present on all SCR's. You must connect a suitable load to test the unit.

  6. questionWhat are the DIP switches used for in my 100P series SCR power control?
    The 100P phase angle SCR (current version) includes a card that is of surface mount construction. The control card has a 6-position selector switch (SW1) that allows the user to easily configure the control. 4-20mA, 0-10V & Input Resistance Selection: The input will accept the standard 4-2 ...

  7. questionWhat is the difference between Zero Fired and Phase Angle Fired SCR Power Controls?
    Phase Angle Fired SCR Power Controls Phase angle SCR power controls adjust the output voltage/wattage by delaying the turn on of the output voltage during each half cycle. The end result is very smooth virtually infinite voltage control. 1) Can be used with resistive or transformer coupled lo ...

 

Ask ISE a Question

   

Headquarters
10100 Royalton Rd.,  Cleveland, OH  44133  USA
Phone: (440) 237-3200  Fax: (440) 237-1744
Email ISE Cleveland
 
Toledo Area Office
417 Tomahawk Drive,  Maumee, Oh 43537
Phone: 419-893-3330 - FAX: 419-893-2151
Email ISE Toledo  
 

ISE, Inc. Privacy Policy

Click for Cleveland, Ohio Forecast Copyright © 2005 ISE, Inc.  All rights reserved.


Powered by ActiveKB Knowledgebase Software